Front Duct Heat Loss 14" BTUH Adjustment for 55°1

Total Linear Feet of Ducting (14" Diameter / R6 Insulation3)

Ambient2 Temperature

20'

40'

60'

80'

100'

60°F

122 244 367 489 611

65°F

183 367 550 733 916

70°F

244 489 733 977 1222

75°F

305 611 916 1222 1527

80°F

367 733 1100 1466 1833

85°F

428 855 1283 1710 2138

90°F

489 977 1466 1955 2443

95°F

550 1100 1649 2199 2749

If you will be ducting the cold air supply and return air to and from a wine cellar, the "heat loss" through the ducting must be considered when sizing the cooling unit. This table calculates the heat loss given: 1) The ambient temperature where the ducting is located, 2) Total length of the ducting, assuming R6 insulation and wine cellar temperature at 55°F. When calculating the thermal load of your wine cellar in a front-ducted application, always consider the BTUH from the table above, and add it to the box load from our other tables.

(1) The table calculates the additional BTUH to be added to box load for the wine cellar, assuming R6 insulation on the ducting and 55°F temperature inside the cellar.

(2) Select the BTUH based on the ambient temperature in the area through which the ducting will be located.

(3) Select the BTUH based on the TOTAL linear feet of ducting (ie add the linear feet for both the supply and return air to/from the wine cellar. It is not necessary to add the linear feet, if any, from ducting the rear (ie hot air supply and return) of the cooling unit.