Sizing Table: 1500-2000 cu ft - AH6500

CellarPro Cooling Systems AH6500 Air Handler

55°F Cooling Capacity1

AH6500 - Low Fan Speed
BTUH 4923   Decibels2 47/52

AH6500 - Medium Fan Speed
BTUH 5350   Decibels2 51/57

AH6500 - High Fan Speed
BTUH 5771   Decibels2 59/62

Cellar Size1

  Ambient
Temperature
  Thermal Load (BTUH)
R12   R19   R30

1500

Cubic Feet

70°F 4608   4346   4188
75°F 4829 4480 4268
80°F 5048 4613 4349
85°F 5269 4746 4429
90°F 5490 4879 4510
95°F 5711 5014 4591
Divider      

1750

Cubic Feet

70°F 5141 4860 4691
75°F 5376 5002 4775
80°F 5612 5144 4861
85°F (5849) 5288 4949
90°F (6085) 5431 5035
95°F (6324) 5576 5124
Divider      

2000

Cubic Feet

70°F (5861) 5556 5372
75°F (6116) 5711 5466
80°F (6373) (5866) 5558
85°F (6630) (6022) 5653
90°F (6888) (6178) 5748
95°F (7146) (6335) (5844)
 

CellarPro Cooling Systems AH6500 Air Handler

60°F Cooling Capacity1

AH6500 - Low Fan Speed
BTUH 5532   Decibels2 47/52

AH6500 - Medium Fan Speed
BTUH 5981   Decibels2 51/57

AH6500 - High Fan Speed
BTUH 6421   Decibels2 59/62

 

Cellar Size1

  Ambient
Temperature
  Thermal Load (BTUH)
R12   R19   R30

1500

Cubic Feet

70°F 4055   3824   3685
75°F 4250 3942 3756
80°F 4442 4059 3827
85°F 4637 4176 3898
90°F 4831 4294 3969
95°F 5026 4412 4040
Divider      

1750

Cubic Feet

70°F 4524 4277 4128
75°F 4731 4402 4202
80°F 4939 4527 4278
85°F 5147 4653 4355
90°F 5355 4779 4431
95°F 5565 4907 4509
Divider      

2000

Cubic Feet

70°F 5158 4889 4727
75°F 5382 5026 4810
80°F 5608 5162 4891
85°F 5834 5299 4975
90°F 6061 5437 5058
95°F 6288 5575 5143

The upper table is shaded to show how the AH6500 air handler cooling system will work at maintaining 55°F, and the lower how the AH6500 air handler cooling system will work at maintaining 60°F, inside the wine cellar using various fan speeds under various thermal loads. The thermal loads are derived from assumptions about the size of the cellar; the R-value in the six cellar surfaces (ie walls, floor and ceiling) and the ambient temperature outside the cellar.

CellarPro AH6500 wine cooling units are designed to maintain optimal wine storage temperatures in wine cellars up to 1750 cubic feet with adequate insulation, and can be operated with the condenser exposed to conditions up to 110°F. For more information, click on our performance and test data.

(1) The thermal loads above are calculated based on the R-Values shown for all walls and ceiling, and a concrete floor. Lower R-Values in the cellar (eg from glass doors) will increase the thermal load on the wine cellar and will require the cooling unit to operate at higher fan speeds. Warmer climates require higher insulation to enable the cooling unit to operate at lower fan speeds. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.

(2) The decibels are listed for the evaporator / condensing unit, both ducted.