3400H Houdini: Sizing Table - Wine Cellars 500-1000 cubic ft

55°F Cooling Capacity

Cooling Unit Output

Low Fan Speed
2737 BTUH
Decibels 56

High Fan Speed
3492 BTUH
Decibels 61

Cellar Size

Ambient
Temperature
Thermal Load (BTUH)
R12R19R30

500

Cubic Feet

70°F211119581867
75°F223820351913
80°F236621121958
85°F249421902006
90°F262222672052
95°F275023452100

600

Cubic Feet

70°F235921922092
75°F250022782143
80°F263923622194
85°F277924462244
90°F292025312296
95°F304026162347

700

Cubic Feet

70°F263024502340
75°F278225422395
80°F298426342452
85°F308627252506
90°F323928182562
95°F339129102617

800

Cubic Feet

70°F290227112596
75°F304028072653
80°F322129042712
85°F338230012771
90°F354130972828
95°F370231942887

900

Cubic Feet

70°F319929952970
75°F337130982933
80°F354232032996
85°F371533073059
90°F388834123122
95°F406135163185

1000

Cubic Feet

70°F339531813052
75°F357632823118
80°F375533983182
85°F393535083248
90°F411636173314
95°F429637263380

60°F Cooling Capacity

Cooling Unit Output

Low Fan Speed
2806 BTUH
Decibels 56

High Fan Speed
3650 BTUH
Decibels 61

Cellar Size

Ambient
Temperature
Thermal Load (BTUH)
R12R19R30

500

Cubic Feet

70°F185817231643
75°F196917911683
80°F208218591723
85°F219619271765
90°F230719951806
95°F242020641848

600

Cubic Feet

70°F207619291841
75°F220020051886
80°F232220791931
85°F244621521975
90°F257022272020
95°F269323022065

700

Cubic Feet

70°F231421562059
75°F244822372108
80°F258223182158
85°F271623982205
90°F285024802255
95°F298425612303

800

Cubic Feet

70°F255423862284
75°F269424702335
80°F283425562387
85°F297626412438
90°F311627252489
95°F325828112541

900

Cubic Feet

70°F281526362614
75°F296627262581
80°F311728192636
85°F326929102692
90°F342130032747
95°F357430942803

1000

Cubic Feet

70°F298827992686
75°F314728952744
80°F330429902800
85°F346330872858
90°F362231832916
95°F378032792974

The tables are shaded to show how the 3400H cooling unit will work at maintaining 55°F (upper table) and 60°F (lower table) inside the wine cellar, using various fan speeds and thermal loads. The thermal loads are derived from assumptions about the size of the cellar, the R-value in the six cellar surfaces (ie walls, floor and ceiling), and the ambient temperature outside the cellar.

CellarPro 3400H wine cooling units are designed to maintain optimal wine storage temperatures in wine cellars up to 1000 cubic feet with adequate insulation, and can be operated with the condenser exposed to conditions up to 95°F.

The thermal loads above are calculated based on the R-Values shown for all walls and ceiling, and a concrete floor. Lower R-Values in the cellar (eg from glass doors) will increase the thermal load on the wine cellar and will require the cooling unit to operate at higher fan speeds. Warmer climates require higher insulation to enable the cooling unit to operate at lower fan speeds. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.

Cells shaded blue indicate loads that exceed the capacity of the cooling units shown in this table.