• Home
  • Cooling Unit Sizing Table 6000S | CellarPro

6000S-EC: Sizing Table - Wine Cellars 1250-1750 cubic ft

55°F Cooling Capacity1

Cooling Unit Output

Low Fan Speed
4311 BTUH
Decibels 54

Medium Fan Speed
4880 BTUH
Decibels 58

High Fan Speed
5046 BTUH
Decibels 66

Cellar Size

Ambient
Temperature
Thermal Load (BTUH)
R12R19R30

1250

Cubic Feet

70°F398837503606
75°F418838713679
80°F438739913751
85°F458841123824
90°F478942353899
95°F499043563972

1500

Cubic Feet

70°F460843464188
75°F482944804268
80°F(5048)46134349
85°F(5269)47464429
90°F(5490)48794510
95°F(5711)50144591

1750

Cubic Feet

70°F(5141)48604691
75°F(5376)50024775
80°F(5612)(5144)4861
85°F(5849)(5288)4949
90°F(6085)(5431)5035
95°F(6324)(5576)(5124)

60°F Cooling Capacity1

Cooling Unit Output

Low Fan Speed
4631 BTUH
Decibels 54

Medium Fan Speed
5279 BTUH
Decibels 58

High Fan Speed
5411 BTUH
Decibels 66

Cellar Size

Ambient
Temperature
Thermal Load (BTUH)
R12R19R30

1250

Cubic Feet

70°F350933003173
75°F368534063238
80°F386135123301
85°F403736193365
90°F421437273431
95°F439138333495

1500

Cubic Feet

70°F405538243685
75°F425039423756
80°F444240593827
85°F463741763898
90°F483142943969
95°F502644124040

1750

Cubic Feet

70°F452442774128
75°F473144024202
80°F493945274278
85°F514746534355
90°F535547794431
95°F(5565)49074509

The upper table shows how the 6000S-EC cooling unit will work at maintaining 55°F, the lower table at maintaining 60°F inside the wine cellar using various fan speeds and under different thermal loads. The thermal loads are derived from assumptions about the size of the cellar; the R-value in the six cellar surfaces (ie walls, floor and ceiling) and the ambient temperature outside the cellar. CellarPro 6000S-EC wine cooling units are designed to maintain optimal wine storage temperatures in wine cellars up to 1750 cubic feet with adequate insulation, and can be operated with the condenser exposed to conditions up to 110°F.

Cells shaded blue indicate loads that exceed the capacity of the cooling units shown in this table.

(1) The thermal loads above are calculated based on the R-Values shown for all walls and ceiling, and a concrete floor. Lower R-Values in the cellar (eg from glass doors) will increase the thermal load on the wine cellar and will require the cooling unit to operate at higher fan speeds. Warmer climates require higher insulation to enable the cooling unit to operate at lower fan speeds. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.