Cooling Capacity - CellarPro 4200VSi @ 60 Degrees


CellarPro Cooling Systems - 4200 Series Cooling Units
Cooling Capacity @ 60°F (1)

4200VSi - Low Fan Speed

BTUH: 3597      Decibels: 54

4200VSi - Medium Fan Speed

BTUH: 3969      Decibels: 59

4200VSi - High Fan Speed

BTUH: 4267      Decibels: 67

Cellar Insulation - Walls, Ceiling & Floor (1)
R12
R19
R30
Cellar Size
Ambient Temperature
Thermal Load
 
70°F
1858 1723 1643
 
75°F
1969 1791 1683
500 Cubic Feet
80°F
2082 1859 1723
 
85°F
2196 1927 1765
 
90°F
2307 1995 1806
 
95°F
2420 2064 1848
 
 
70°F
2465 2302 2203
 
75°F
2602 2385 2253
750 Cubic Feet
80°F
2739 2467 2302
 
85°F
2877 2550 2351
 
90°F
3014 2634 2402
 
95°F
3152 2717 2453
 
 
70°F
2988 2799 2686
 
75°F
3147 2895 2744
1000 Cubic Feet
80°F
3304 2990 2800
 
85°F
3463 3087 2858
 
90°F
3622 3183 2916
 
95°F
3780 3279 2974
 
 
70°F
3509 3300 3173
 
75°F
3685 3406 3238
1250 Cubic Feet
80°F
3861 3512 3301
 
85°F
4037 3619 3365
 
90°F
4214 3727 3431
 
95°F
X 3833 3495
 
 
70°F
4055 3824 3685
 
75°F
4250 3942 3756
1500 Cubic Feet
80°F
X 4059 3827
 
85°F
X 4176 3898
 
90°F
X 4267 3969
 
95°F
X X 4040

Legend
The table is shaded to show how the 4200 cooling unit will work at 55°F using various fan speeds under various thermal loads. The thermal loads are derived from assumptions about the size of the cellar; the R-value in the six cellar surfaces (ie walls, floor and ceiling) and the ambient temperature outside the cellar, as follows:

  • The light-shaded numbers represent thermal loads that are within the capacity of the cooling unit at the low fan speed
  • The medium-shaded numbers represent thermal loads that are within the capacity of the cooling unit at the medium fan speed
  • The dark-shaded numbers represent thermal loads that are within the capacity of the cooling unit at the high fan speed
  • "X" indicates conditions that are beyond the capacity of our 4200 Series cooling units

Summary
CellarPro 4200 wine cooling units are designed to maintain 55°F temperatures in wine cellars up to 1000 cubic feet with adequate insulation, and can be operated with the condenser exposed to conditions up to 115°F. For more information, click on our 4200VS performance and test data.

Please note:   The thermal loads above are calculated based on the R-Values shown for all walls, floor and ceiling. Lower R-Values in the cellar (eg from glass doors) will increase the thermal load on the wine cellar and will require the cooling unit to operate at higher fan speeds. Warmer climates require higher insulation to enable the cooling unit to operate at lower fan speeds. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.

(1) For reference purposes, the calculated BTUH at 55°F for Breezaire WKL 4000 is 3351 and WhisperKool XLT 4200 is 3084.