1800H 220V: Sizing Table - Wine Cellars 2.83-11.3 cu meters

Cooling Unit Output

Low Fan Speed
12.8°C:1520 BTUH
15.6°C:1637 BTUH
Decibels 49

High Fan Speed
12.8°C:1731 BTUH
15.6°C:1864 BTUH
Decibels 55

Cellar Size

Ambient
Temperature
Thermal Load (BTUH)
12.8°C Cellar Temp15.6°C Cellar Temp
R12R19R12R19

2.8

Cubic Meters

18°C956912841803
24°C1068979940862
29°C118010461038920
35°C129111141136980

5.7

Cubic Meters

18°C1220115710741018
24°C1380125312141103
29°C1538134913531187
35°C1699144614951272

8.5

Cubic Meters

18°C1501142213211251
24°C1700154214961357
29°C(1900)166216721463
35°C(2100)178318481558

11.3

Cubic Meters

18°C1698160914941416
24°C(1921)174416901535
29°C(2146)(1879)(1888)1654
35°C(2369)(2015)(2085)1773

(1) The table is shaded to show which cooling units will work at 12.8°C and 15.6°C under various thermal loads. The thermal loads are derived from assumptions about the size of the cellar; the R-value in the six cellar surfaces (ie walls, floor and ceiling) and the ambient temperature outside the cellar.

Cells shaded blue indicate loads that exceed the capacity of the cooling units shown in this table.

We provide the estimated thermal loads for various-size wine cellars across a range of ambient temperatures and with different R-Values to help you select the appropriate CellarPro wine cooling unit for your cellar. The thermal loads are calculated based on the R-Values shown for all walls and ceiling, and a concrete floor. Lower R-Values in the cellar (eg from glass doors or uninsulated concrete walls) will increase the thermal load on the wine cellar. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.